Ceiling-Mounted Dual-Side Air Coolers
- Optimized Heat Exchange Performance
Combining fluid dynamics and aerodynamic analysis, the unit features an optimized airflow structure that minimizes pressure drop and maximizes heat exchange efficiency. The enhanced refrigerant distribution system ensures consistent performance across varying operating conditions, delivering faster cooling and improved system stability. - Durable, Corrosion-Resistant Construction
The unit uses high-strength aluminum fins with near-90° punching angles to maximize contact area with copper tubes, boosting heat transfer efficiency. These fins have passed 500-hour salt spray testing for superior corrosion resistance. The unit shell is constructed from hot-dip galvanized steel—offering 3x the corrosion resistance of electro-galvanized steel—with phosphating electrostatic spraying for a robust, aesthetic finish. - Reliable Exterior Rotor Motor
Equipped with high-quality exterior rotor motors, the unit operates reliably across an extreme temperature range of -40°C to +75°C. The grille fan guard ensures uniform airflow and enhanced safety, while delivering consistent air volume for effective cooling. - Advanced Double-Layer Water Collection Pan
The dual-layer aluminum water tray efficiently collects water generated during defrosting, enabling secondary defrosting to boost cooling performance. Its optimized design improves ventilation and accelerates cooling, while high-quality, rust-resistant materials ensure long-term durability. - Designed for quiet operation, uniform air distribution, and rapid cooling, this evaporator unit is the ideal choice for demanding livestock and industrial cooling applications.
Brand
BAIFUTE
Model
BFT-GL,BFT-GD
Diameter(mm)
400
Air Flow(m³/h)
3149-11892
Fin Space
4.5.6.0
Power
216-864
Evaporating Area
30-120
Defrosting
Electric Heater
| Ceiling-Mounted Dual-Side Air Coolers | ||||||||
|---|---|---|---|---|---|---|---|---|
| MODEL | EVAPORATING AREA | MOTOR AC 380V/50Hz/3ph | HEATER AC 220V | |||||
| DIAMETER | AMOUNT | AIR VOLUME | MAX RANGE | POWER | CURRENT | POWER | ||
| m2 | mm | m3/h | m | W | A | kW | ||
| BFT-GL30-T | 30 | 400 | 1 | 3149 | 15 | 216 | 0.46 | 2.3 |
| BFT-GD20-T | 20 | 3241 | 3.5 | |||||
| BFT-GL40-T | 40 | 400 | 2 | 6299 | 15 | 432 | 0.92 | 3.5 |
| BFT-GD30-T | 30 | 6483 | 5.2 | |||||
| BFT-GL60-T | 60 | 400 | 2 | 5643 | 15 | 432 | 0.92 | 3.5 |
| BFT-GD40-T | 40 | 5946 | 5.2 | |||||
| BFT-GL80-T | 80 | 400 | 3 | 8465 | 15 | 648 | 1.38 | 4.9 |
| BFT-GD60-T | 60 | 8919 | 7.3 | |||||
| BFT-GL100-T | 100 | 400 | 4 | 12597 | 15 | 864 | 1.84 | 7 |
| BFT-GD80-T | 80 | 12966 | 10.5 | |||||
| BFT-GL120-T | 120 | 400 | 4 | 11286 | 15 | 864 | 1.84 | 7 |
| BFT-GD100-T | 100 | 11892 | 10.5 | |||||
| Fin Spacing:4.5mm Suitable Room Temperature>5℃ | ||||||||
| Fin Spacing:6mm Suitable Room Temperature>-18℃ | ||||||||
| MODEL | DIMENSIONS | INSTALLATION DIMENSIONS | INLET | OUTLET | DRAIN DIAM | |||
| L | W | H | L´ | W´ | ||||
| mm | mm | mm | mm | mm | mm | mm | in | |
| BFT-GL30-T | 964 | 881 | 446 | 640 | 943 | Φ12 | Φ22 | G1" Thread G7/8" Bent connector |
| BFT-GD20-T | ||||||||
| BFT-GL40-T | 1314 | 910 | 990 | 993 | Φ12 | Φ22 | ||
| BFT-GD30-T | ||||||||
| BFT-GL60-T | 1314 | 990 | Φ12 | Φ22 | ||||
| BFT-GD40-T | ||||||||
| BFT-GL80-T | 1764 | 1440 | Φ16 | Φ25 | ||||
| BFT-GD60-T | ||||||||
| BFT-GL100-T | 2464 | 2140 | Φ16 | Φ25 | ||||
| BFT-GD80-T | ||||||||
| BFT-GL120-T | 2464 | 2140 | Φ19 | Φ25 | ||||
| BFT-GD100-T | ||||||||